COSC 325

Lecture note #6

Heat loss and heat gain in buildings: Outside air (OA)

1.00 Outside air

1.01 Infiltration

1.02 Ventilation

2.00 Calculation of hg/hl due to outside air (OA)

3.00 Value of CFM to be used in calculation

4.00 Some explanations of the constants used in OA heat transfer models



Question: A 32' long, 25' wide, 12' high room has an infiltration rate of 2.5 ACH. What is the rate of infiltration of outside air into that room in CFM?

Question: What would be the quantity of sensible heat loss by a building due to the effect of infitrated air at the rate of 250 CFM, when the indoor and outdoor dB temperatures are 70 and 20 deg. F respectively?

Question: Rate of infiltration in a 40' long, 30' wide, 12' high room is 0.75 ACH. At an inside dB temperature of 75 deg. F with 50% RH and an outside dB temperature of 95 deg. F with 40% RH, what would be the latent heat gain inside the room due to infiltrated air?